Where are backflow devices required?

Backflow prevention devices are required in a wide range of residential, commercial, industrial and agricultural applications to protect drinking water supplies from contamination. Where a backflow prevention device is required, and the type of device suitable for the application, depends on the potential contamination risk, the property’s water supply arrangements and the relevant plumbing and water authority requirements. Each fixture, zone, or containment is give a Hazard Rating and subsequently matched with a suitable type of backflow prevention.

The following guide provides examples of activities, equipment and premises where backflow prevention may be required, along with their associated hazard ratings and typical device requirements. It is intended to help property owners, facility managers, plumbers and businesses understand where backflow prevention may be necessary.

The information provided in this guide is for general information purposes only. It is not a substitute for a site-specific backflow risk assessment or inspection. The actual backflow prevention requirements for a property can vary depending on its plumbing configuration, water supply connections, activities undertaken and potential contamination risks.

A qualified and appropriately accredited backflow specialist should inspect the property and assess the relevant hazards to determine the appropriate backflow prevention requirements. Final requirements must also comply with applicable Australian Standards, plumbing regulations and the relevant water authority’s requirements.

Backflow hazard ratings are used to determine the potential risk that a particular installation or activity poses to the drinking water supply. The hazard classification helps determine the appropriate level of backflow protection required.

The three general hazard classifications are:

  • High Hazard: Water contains contaminants capable of causing serious illness or death if introduced into the drinking water supply.
  • Medium Hazard: Water could contain substances that may cause illness but are unlikely to present a serious health risk.
  • Low Hazard: A backflow situation where the it would be considered a nuisance if it were to occur. Such as the water would not pose a health risk but may affect taste, colour or appearance.

The hazard classification is an important consideration when determining the type of backflow prevention device required.

Legend:
AG = air gap
AVB = atmospheric vacuum breaker
DCDA = double check detector assembly
DCV = double check valve
RAG = registered air gap
RBT = registered break tank
RPDA = reduced pressure detector assembly
RPZD = reduced pressure zone device
SCDAT = single check detector assembly (testable)
SCVT = single check valve (testable)

AGRICULTURAL, HORTICULTURAL AND IRRIGATION SYSTEMS

Form of cross-connectionHazard ratingBackflow prevention device
Antibiotic injectorsHighRBT or RPZD
Irrigation systems injected with fertilizers, herbicides,
nematicides and insecticides
HighRBT or RPZD
Fogging and cleaning sprays with chemical injectionHighRBT or RPZD
Drinking nipples and troughsHighRAG or RBT or RPZD
Irrigation systems
Outlets less than 150 mm above finished surface level and not involving injection systems
MediumTestable device

INDUSTRIAL AND COMMERCIAL

Form of cross-connectionHazard ratingBackflow prevention device
Fogging and cleaning spray equipment with chemical injection or additiveHighRBT or RPZD
Pan washing apparatusHighRBT or RPZD
Chemical dispensers (high toxicity)HighRAG, RBT or RPZD
Weed and pest spraying and water cartage tanksHighRAG or RPZD
Mixing of chemicalsHighRAG or RPZD
Portable and mobile tankersHighRAG or RPZD
Chemical dispensers (low toxicity)MediumTestable device
Coils and jackets in heat exchangers—unsealed and toxic
environment
MediumDCV
Coils and jackets in heat exchangers—sealed and non-toxic environmentsLowNon-testable device
Photographic processing machines (no developer mixing)LowNon-testable device
Electroplating, degreasing, descaling, stripping, pickling,
dipping, etc., tanks, vats and vessels
HighRBT or RPZD
Commercial laundriesHighRAG or RPZD
Cooling or heating systems with recirculating waterHighRAG or RPZD
Clean-in-place systems (i.e. internal chemical cleaning takes
place without dismantling equipment)
HighRAG or RPZD
Dockside facilitiesHighRAG or RPZD
Industrial process water that has been recirculatedHighRAG or RPZD
Industrial and teaching laboratoriesHighRAG or RPZD
Aircraft facilitiesMediumTestable device
Secondary school laboratories (including fume cupboards)MediumTestable device
Water filtration equipmentLowNon-testable device

HOSPITALS/MEDICAL LABORATORIES, NURSING HOMES

Form of cross-connectionHazard ratingBackflow prevention device
Equipment used for handling, mixing, measuring and processing
chemical and microbiological substances
HighRAG or RPZD
Photographic developers. Developer mixing facilitiesHighRAG or RPZD
Dental consoleHighRAG or RPZD
Haemodialysis machinesHighRAG or RPZD
Dissecting rooms in hospitals and medical buildingsHighRBT or RPZD
Mortuary equipment used in funeral parlours, mortuaries,
autopsy areas
HighRBT or RPZD
Utility rooms, where other than handbasins are installedHighRBT or RPZD
Operating theatres in hospitals and medical buildingsHighRBT or RPZD
Dental and medical surgeriesHighRAG or RPZD

FIXTURES AND APPLIANCES

Form of cross-connectionHazard ratingBackflow prevention device
BidetsHighRBT or RPZD
Food preparation or food storage tanks, vats and vessels with clean-in-place systemsHighRAG or RPZD
Fixtures used for food preparation, e.g. sinksLowAG
Fixtures used for ablutions, e.g. baths, bidettes, basins, showersLowAG
Laundry troughsLowAG
Hair salons basins or troughsLowNon-testable device
Carbonated drink dispensing machinesLowStainless steel dual CV
(intermediate) vent
Drink-dispensing equipment, vending machines, coffee machinesLowNon-testable device
Food preparation or food storage tanks, vats and vesselsLowAG/non-testable device
Sanitary dump pointsHighRAG or RPZD
Food storage tanks, vats and vessels with clean-in-place systemsHighRAG or RPZD
Food storage tanks, vats and vesselsLowNon-testable device

HOSE ATTACHMENT OUTLETS

Form of cross-connectionHazard ratingBackflow prevention device
External hose tapsLowNon-testable device
Hose taps located within 18 m of a zone-protected areaSame hazard rating as zone protected areaVarious depending on hazard rating

WATER SUPPLY SYSTEMS PERMANENTLY ATTACHED

Form of cross-connectionHazard ratingBackflow prevention device
Steam boilersLowBT
Cooling towersHighRAG or RPZD
Steam calorifierMediumTestable device

WATER TREATMENT SYSTEMS

Form of cross-connectionHazard ratingBackflow prevention device
Demineralizing equipment using ion-exchange resins with acid and alkali regenerationHighRBT or RPZD
Plants with auxiliary non-drinking water suppliesHighRBT or RPZD
Drinking water in reclaimed water plantsLowNon-testable device
ChlorinatorsMediumTestable device
In-line water softeners and filtersLowNon-testable device

FIRE SERVICES

Form of cross-connectionHazard ratingBackflow prevention device
Fire hose reels located in areas of hazard have to have a backflow prevention device in line with the hazard ratings of the areas within reach of the fire hoseMediumDCV
Home fire sprinklers systemsLowDCV or Dual CV
Bushfire water spray systemsLowNon-testable device or AG

CONTAINMENT PROTECTION

Form of cross-connectionHazard ratingBackflow prevention
device
Premises with an alternative water supply excluding rainwater tanksHighRBT or RPZD
Premises where inspection is restrictedHighRBT or RPZD
Hospitals, mortuaries, clinics and the likeHighRBT or RPZD
Piers, docks and other waterfront facilitiesHighRBT or RPZD
Sewage treatment plants and sewage lift stationsHighRBT or RPZD
Chemical plantsHighRBT or RPZD
Metal finishing plantsHighRBT or RPZD
Petroleum processing or storage plantsHighRBT or RPZD
Radioactive material processing plants or nuclear reactorsHighRBT or RPZD
Car and plant washing facilitiesHighRBT or RPZD
AbattoirsHighRBT or RPZD
Factories using processing or manufacturing toxic chemicalsHighRBT or RPZD
Chemical laboratoriesHighRBT or RPZD
Pathology laboratoriesHighRBT or RPZD
Sanitary depotsHighRBT or RPZD
UniversitiesHighRBT or RPZD
Food and beverage processing plantsMediumTestable device
Caravan parksMediumTestable device
MarinasMediumTestable device
Premises with greywater re-use systemsMediumTestable device
Public swimming poolsMediumTestable device
Premises with reticulated and disinfected reclaimed water systemsMediumTestable device
Premises with rainwater tanks – BuriedMediumTestable device
Premises with rainwater tanks – Partly buriedMediumTestable device
Premises with rainwater tanks – Above groundLowNon-testable device
Premises with reticulated recycled water systemLowNon-testable device
Premises with reticulated recycled water systemLowNon-testable device
All premises fire services Low LowSCVT or SCDAT
All premises fire services MediumMediumDCV or DCDA
All premises fire services HighHighRBT or RPZD or RPDA

Why a Property Inspection Is Important

While industry tables and hazard classifications provide a useful guide, they cannot identify every potential backflow risk within a property.

Two properties undertaking similar activities may have different backflow prevention requirements due to differences in their plumbing arrangements, water connections, equipment and potential contamination sources.

A site inspection allows a backflow specialist to assess the actual installation, identify potential cross-connections and determine whether suitable backflow prevention measures are in place.

Backflow Prevention Assessments and Compliance

Central Coast Backflow Specialist provides professional backflow prevention services for commercial, industrial, agricultural and other properties across the Central Coast, Newcastle and Lake Macquarie.

Our services include backflow prevention testing, device installation, repairs, commissioning and compliance management. We can help identify potential backflow risks, assess existing installations and assist property owners and facility managers with their backflow prevention responsibilities.